Symbol
Model choice belongs to each placed Transformer component. Changing one component does not change other instances or the default for future placements.
Ideal
Turns ratio only, with no magnetizing, leakage, or winding loss.
- AC sweep
- Transient
Model definition
The Ideal model enforces the signed turns ratio between each winding and the first primary winding. A negative turns value reverses that winding's dot polarity.
It transfers voltage, current, and impedance without magnetizing current, leakage flux, copper loss, core loss, or saturation.
Equations
Parameters
This model has no editable model parameters.
Limits
- No-load current is zero.
- Leakage inductance, winding resistance, core loss, and saturation are omitted.
- Only AC sweep and Transient analyses are qualified.
Linear
Adds magnetizing inductance, finite coupling/leakage, and winding resistance. No saturation.
- AC sweep
- Transient
Model definition
The Linear model represents each winding with an inductor and series resistance, then couples the inductors with the selected coupling coefficient.
Magnetizing inductance is primary-referred. OhmSpice scales every other winding inductance by the square of its signed turns ratio.
Equations
Parameters
| Parameter | Default | Accepted values |
|---|---|---|
| Magnetizing inductancePrimary-referred magnetizing inductance. | 10 mH | Greater than 0 |
| CouplingCoupling coefficient between windings (0 to 1, exclusive). | 0.999 | Greater than 0 and less than 1 |
| Winding resistanceSeries resistance applied to each winding. | 100 mΩ | At least 0 |
Limits
- The core remains linear, with no saturation, hysteresis, or frequency-dependent core loss.
- The same winding-resistance value applies to every winding.
- Coupling must remain below 1 because exact unity coupling is singular in this formulation.